BRONKHORST®
Page24DeviceNetinterface 9.17.026
4.2.2 Setpoint
FortheobjectsAnalogSensorandSingleStage Controller,thefollowing data typesanddataunits aresupported for
Value and alarm levels. Note that data type and data unit can only be changed when not in executing mode. The
followingsdataunitsaresupported(dependentonsensortype,actualsensor
typecanbefoundincalibrationsheet):
Sensortype Supportedunits
0(pressure) 0x1001(counts)
0x1007(percentage)[notforSensorvalue]
0x1300(psi)
0x1301(Torr)
0x1303(mmHg)
0x1305(cmH
2
O)
0x1307(bar)
0x1308(mbar)
0x1309(Pa)
0x130A(kPa)
0x130B(atm)
0x130C(gf/cm
2
)
0x0800(cmHg)
0x0801(kgf/cm
2
)
1(liq.Volume) 0x1001(counts)
0x1007(percentage)[notforSensorvalue]
0x0900(l/min)
0x0901(ml/h)
0x0902(ml/min)
0x0903(l/h)
0x0904(mm
3
/s)
0x0905(cm
3
/min)
2(massflow) 0x1001(counts)
0x1007(percentage)[notforSensorvalue]
0x1404(kg/s)
0x140E(mg/min)
0x140F(g/min)
0x1410(kg/h)
0x0A00(kg/min)
0x0A01(g/h)
0x0A02(g/s)
0x0A03(mg/h)
0x0A04(mg/s)
3(gasvolume) 0x1001(counts)
0x1007(percentage)[notforSensorvalue]
0x1400(sccm)
0x1401(slm)
0x0B00(ln/min)
0x0B01(mln/h)
0x0B02(mln/min)
0x0B03(ln/h)
0x0B04(m
3
n/h)
0x0B05(mls/min)
0x0B06(mls/h)
0x0B07(ls/h)
0x0B08(m
3
s/h)
0x0B09(ls/min)
4(other) 0x1001(counts)
0x1007(percentage)[notforSensorvalue]
5(temperature) 0x1001 (counts)
0x1007(percentage)[notforSensorvalue]
0x1200(deg.C)
0x1201(deg.F)
0x1202(K)
Thefollowingdatatypesaresupported: 0xC3(int) 0xCA(real)