Parameter
number
(DDE)
Parameter
name
Group
0
Group
1
Group
2
Process
number
FB
nr
(par)
Var
Type
Var
Length
Min
value
Max
value
Read Write Poll Secured Highly
Secured
Default Value Description
2011-05-18 Page 2 of 5FlowDDE database version V3.64
DDE str
66 <CalRegFS2> 9 116 4 l 0 16777215 Yes Yes No Yes No 52A513 calibration register full scale input 2 ADCCalRegFS2
67 ADC control register 9 114 4 l 0 4294967295 Yes Yes No Yes No 18904E ADC control registerADCcntrReg
68 Bridge potmeter 9 116 5 c 0 255 Yes Yes No Yes No 0 sensor bridge zero potmeter settingBridgePotm
69 <AlarmEnble> 4 115 4 c 0 255 Yes Yes No Yes No 1 broadcast alarm messsage enable flagAlarmEnble
70 Test mode 4 115 5 c 0 255 Yes Yes No Yes No 0 test mode selection (not active until cntrlmode has been set to value 5)TestMode
71 <ADC channel select> 9 115 6 c 1 32 Yes Yes No Yes No 1 channel selection ADCChanSelect
72 Normal step controller response 8 114 5 c 0 255 Yes Yes No Yes No 0 controller response for normal steps (128=normal, <128=slower, >128=faster)ContrResp
73 Setpoint exponential smoothing filter 6 117 3 f 0 1 Yes Yes No Yes No 1.0 analog input filter constant (0=max, 1=min)ErrInFilCo
74 Sensor exponential smoothing filter 6 117 4 f 0 1 Yes Yes No Yes No 1.0 sensor input filter constant (0=max, 1=min)ExpSmooCon
75 Analog output zero scale 10 21 i -32767 65535 Yes Yes No Yes No 32767 analog output correction factor zero scale (meas outp DSCM-A 0=0 other 32767=0)AnOutCorZS
76 Analog output full scale 10 22 i 0 65535 Yes Yes No Yes No 2000 analog output correction factor full scale (meas outp 2000 = 1 * multiplication)AnOutCorFS
77 Analog input zero scale 10 23 i -32767 65535 Yes Yes No Yes No 32767 analog input correction factor zero scale (ext setp DSCM-A 0=0 other 32767=0)AnInpCorZS
78 Analog input full scale 10 24 i 0 65535 Yes Yes No Yes No 2000 analog input correction factor full scale (ext setp 2000 = 1 * multiplication)AnInpCorFS
79 Tuning mode 7 115 7 c 0 255 Yes Yes No Yes No 0 (auto)tuning mode selection (not active until cntrlmode has been set to value 6)TuningMode
80 Valve default 8 114 6 c 0 255 Yes Yes No Yes No 0 valve type (needed for controlling behaviour)DefVlvType
81 Global modify 12 0 19 c 0 255 Yes Yes No No No 0 contains number(s) of changed processes for indirect polling (0xXX / 0xFF)GlobModify
82 Valve span correction factor 8 114 7 f 0 1 Yes Yes No Yes No 0.1 correction factor valve curve ratio high/low areaSpanCorr
83 Valve curve correction 8 114 8 c -2 Yes Yes No Yes No 20,80 Valve curve correction for controller (max. factor*0.1, flow where factor = 1)VlvCrvStps
84 <MemShipNor> 8 114 9 c -2 Yes Yes No Yes No 10,5000,10,5000 array with memberships for normal Fuzzy controllerMemShipNor
85 <MemShipOpn> 8 114 10 c -2 Yes Yes No Yes No
1,10000,3750,20000
array with memberships for 0-open Fuzzy controllerMemShipOpn
86 IO status 12 20 114 11 c 0 255 Yes Yes No Yes No 4 IO status byte for jumper settings and LED signal modesIOStatus
87 <FuzzStNeNo> 8 114 13 c -2 Yes Yes No Yes No -30000,-500,-50 array with neg nor output steps for Fuzzy contr.FuzzStNeNo
88 <FuzzStPoNo> 8 114 14 c -2 Yes Yes No Yes No 50,500,25000 array with pos nor output steps for Fuzzy contr.FuzzStPoNo
89 <FuzzStOpen> 8 114 15 c -2 Yes Yes No Yes No 90,180,12000 array with open at 0 output steps for Fuzzy contr.FuzzStOpen
90 Device type 13 113 1 c 6 Yes No No No No DMFC (FLOW-BUS) device type information stringDeviceType
91 BHTModel number 13 113 2 c -2 Yes Yes No Yes No F201C-FA model number information stringModelNum
92 Serial number 13 113 3 c -2 Yes Yes No Yes Yes SN999999A serial number information string (to be changed by Bronkhorst only)SerialNum
93 Customer model 11 113 4 c -2 Yes Yes No Yes No STANDARD manufacturing configuration information stringMfrConfig
94 BHT1 14 118 1 c -2 Yes Yes No Yes Yes 01,01,95 special BHT parameter (to be changed by Bronkhorst only)BHT1
95 BHT2 14 118 2 i 0 65535 Yes No No No No 0 special BHT parameterBHT2
96 BHT3 14 118 3 l -3000000000 3000000000 Yes No No No No 0 special BHT parameterBHT3
97 BHT4 14 118 4 i 0 65535 Yes No No No No 0 special BHT parameterBHT4
98 BHT5 14 118 5 c 0 255 Yes No No No No 0 special BHT parameterBHT5
99 BHT6 14 118 6 c 0 255 Yes Yes No No No 0 special BHT parameterBHT6
100 BHT7 14 118 7 c 0 255 Yes No No No No 0 special BHT parameterBHT7
101 BHT8 14 118 8 c 0 255 Yes No No No No 0 special BHT parameterBHT8
102 BHT9 14 118 9 l -3000000000 3000000000 Yes No No No No 0 special BHT parameterBHT9
103 BHT10 14 118 10 c 0 1 No Yes No Yes Yes 0 special BHT parameter (to be changed by Bronkhorst only)BHT10
104 Broadcast repeating time 8 114 16 c 0 255 Yes Yes No Yes No 128 broadcast repeating time (x5 ms) (old:height of open at 0 pulse train for valve)PulseHight
105 Firmware version 13 20 113 5 c 6 Yes No No No No VX.XX revision number of firmwareVersion
106 Pressure sensor type 20 115 9 c 0 255 Yes Yes No Yes No 0 type of pressure sensorPressSensr
107 Barometer pressure 20 116 8 f 0 1200 Yes Yes No No No 1013.25 mbar atmospheric (central) barometer pressureBaroPress
108 Sensor input zero scale 10 25 i -32767 65535 Yes Yes No Yes No 32767 analog sensor signal input corr. factor zero scale (DSCM-A 0=0 other 32767=0)AnIn1CorZS
109 Sensor input full scale 10 26 i 0 65535 Yes Yes No Yes No 2000 analog sensor signal input correction factor full scale (2000=1*multiplication)AnIn1CorFS
110 Reference voltage input zero scale 10 27 i -32767 65535 Yes Yes No Yes No 32767 analog Vref input correction factor zero scale (DSCM-A 0=0 other 32767=0)AnIn2CorZS
111 Reference voltage input full scale 10 28 i 0 65535 Yes Yes No Yes No 2000 analog Vref input correction factor full scale (2000=1*multiplication)AnIn2CorFS
112 Analog setpoint zero scale 10 29 i -32767 65535 Yes Yes No Yes No 32767 analog setpoint output correction factor zero scale (DSCM-A 0=0 other 32767=0)AnOu1CorZS
113 Analog setpoint full scale 10 30 i 0 65535 Yes Yes No Yes No 2000 analog setpoint output correction factor full scale (2000=1*multiplication)AnOu1CorFS
114 Reset 12 115 8 c 0 255 No Yes No No No 0 reset facilities (program/alarm/batchcounter)Reset
115 User tag 11 113 6 c -2 Yes Yes No No No USERTAG user definable alias stringUserTag
116 Alarm limit maximum 15 97 1 i 0 41600 Yes Yes No No No 0 maximum limit for sensor signal to trigger alarm situationAlrmMaxLim
117 Alarm limit minimum 15 97 2 i 0 41600 Yes Yes No No No 0 minimum limit for sensor signal to trigger alarm situationAlrmMinLim
118 Alarm mode 15 97 3 c 0 255 Yes Yes No No No 0 alarm modeAlrmMode
119 Alarm output mode 15 97 4 c 0 255 Yes Yes No No No 0 alarm relais activity mode during alarm situationAlrmOutMod
120 Alarm setpoint mode 15 97 5 c 0 1 Yes Yes No No No 0 setpoint change enable during alarm situationAlrmStpMod
121 Alarm new setpoint 15 97 6 i 0 32767 Yes Yes No No No 0 new/safe setpoint during alarm situation (until reset)AlrmNwSetp
122 Counter value 16 104 1 f 0 3.40282E+38 Yes Yes Yes No No 0 actual counter valueCntrValue
123 Counter unit index 16 104 2 c 0 31 Yes Yes No No No 0 pointer to counter unit (classic counter unit table)CntrUnit
124 Counter limit 16 104 3 f 0 3.40282E+38 Yes Yes No No No 0 counter limit/batchCntrLimit
125 Counter output mode 16 104 4 c 0 255 Yes Yes No No No 0 counter relais activity mode when limit/batch has been reachedCntrOutMod
126 Counter setpoint mode 16 104 5 c 0 1 Yes Yes No No No 0 setpoint change enable during counter limit/batch situation (until reset)CntrStpMod
127 Counter new setpoint 16 104 6 i 0 32767 Yes Yes No No No 0 new/safe setpoint at counter limit/batch situation (until reset) (normally = 0%)CntrNwSetp
128 Counter unit 16 104 7 c 4 Yes Yes No No No ln counter readout unit (informative only for older devices)CntrUntstr
129 Capacity unit 3 19 31 c 7 Yes Yes No Yes No ln/min capacity readout unit (informative only for older devices)capunitstr
130 Counter mode 16 104 8 c 0 255 Yes Yes No No No 0 counter modeCntrMode
131 Minimum hardware revision 13 113 7 c 1 Yes No No No No VX.XX minimum required hardware revision level for firmware versionHwRev
132 <RCreadfact> 17 1 f 1E-10 10000000000 Yes No No No No 1.0 readout factor for direct reading (changes with readunit: local on module, R.O.)RCreadfact
133 <channumber> 17 2 c 1 120 Yes Yes No No No 1 channel number for operationchannumber
134 <masterchan> 17 3 c 0 120 Yes Yes No No No 0 master channel for master-slave operationmasterchan
135 <RCslavefct> 17 4 i 0 32000 Yes Yes No No No 32000 RC slave factorRCslavefct