
BRONKHORST HIGH-TECH B.V.
6 TROUBLESHOOTING
6.1 General
For a correct analysis of the proper operation of a mass flow meter/controller it is recommended to remove
the unit from the process line and to check it without applying gas supply pressure. In case the unit is dirty,
this can be ascertained immediately by loosening the compression type couplings and, if applicable, the
flange on the inlet side.
Energizing or de-energizing of the instrument may already indicate whether there is an electronic failure.
After that gas pressure is to be applied in order to check flow behaviour.
If there should be suspicion of leakage do not check for bubbles with a leak detection liquid as this may lead
to a short-circuit in the sensor capillary assembly or p.c. board.
6.2 Troubleshooting summary
1b) check cable connection
Output stage blown-up due to long
lasting shortage and/or high-voltage
Supply pressure too high, or differential
pressure across meter too high
1d) lower supply pressure
Valve blocked/contaminated
Screen in inlet fitting blocked
Output signal much lower than
setpoint signal or desired flow
Screen blocked/contamined
LFD blocked/contaminated and/or liquid
in meter
Valve blocked/contaminated
Valve internals damage (swollen seat in
plunger)
Incorrect type of gas is used and/or
pressure/diff. pressure
3e) try instrument on conditions for which
it was designed
Flow is gradually decreasing
Condensation, occurs with
,
hydrocarbons such as
4a) decrease supply pressure and/or
heat gas to be measured
Valve adjustment has changed
Supply pressure/diff. pressure too high
Pipeline too short between pressure
regulator and MFC
5b) increase length or diameter of piping
upstream
Pressure regulator is oscillating
5c) replace pressure regulator or try ‘5b’
Valve sleeve or internals damaged
Controller adjustment wrong
Small flow at zero setpoint
Valve leaks due to damaged plunger or
dirt in orifice
Pressure too high or much too low
6b) apply correct pressure
9.17.028 page 23
Komentarze do niniejszej Instrukcji